Atlanta (AT1) Atlanta (AT2/AT3) Boston Buffalo Chicago Cleveland Dallas 2323 Bryan Dallas 4101 Bryan Dallas INFOMART Denver Detroit Indianapolis Los Angeles Miami 1st Miami 2nd Nashville New Jersey NYC 60 Hudson NYC 65 Broadway NYC 111 8th Palo Alto Philadelphia Broad Philadelphia Market Phoenix Pittsburgh Reston Saint Louis San Jose Seattle 3rd Seattle 6th Sunnyvale Tampa Toronto Vienna SAIC Vienna Tyco

Atlanta (AT1) Data Center

180 Peachtree Street NW, Atlanta, GA 30303, USA

See other Atlanta sites:

Data Center Building Specs

Building Specs

Equinix is located in a 500,000 SF, fully dedicated carrier hotel/interconnect facility that is home to the Southeast's largest concentration of telecommunication companies.

  
Square Feet79,201
Floor Load115 pounds per square foot
Ceiling HeightNine feet nine inches above raised floor
Roof RightsRoof rights available
Line of SiteEach request will need to be verified as new buildings are being constructed
NPA-NXX404-525
FiberThree fiber entry points
Fiber ConduitsFourteen 4 inch conduits
Fiber InnerductsForty-two inner ducts three 1-inch inner ducts per conduit
KVM CartKVM cart available upon request
  
Data Center Environmental Controlsl
  

Environmental Controls

  
Fire SupressionPre-action, dry pipe sprinkler system
HVACA/C units maintain a climate of 72 degrees (+/- 5) and 30-60% humidity, N+1 redundancy
Data Center Power Systems
  

Power Systems

  
Power Density 6.0KW Max per Cab (utilization)
UPS System (2) 2360 KW UPS Systems (phase 1)
Each System is deployed as N + 1
UPS Battery backup systems are deployed to carry full design load for 15 minutes
UPS distribution systems support 4720 KW primary with 30% additional for redundant circuits
DC Plant 192 KW DC System (phase 1)
System is deployed as 2N with dedicated A&B plants
DC Battery backup system are designed and deployed to carry full load for 2 hours per each plant
DC distribution systems support 192 KW primary with 30% additional for redundant circuits
Standby Generator2250 KW generator systems
System is deployed as N+1
Dedicated fuel system designed and deployed to sustain continuous operation at full design load for 24 hours.
  
Data Center Power Systems
  

Security Systems

  
Security SystemsLobby security, real-time video surveillance with 24x7 monitoring, card key access, alarm/key monitoring, and CCTV surveillance
Data Center Connectivity
  

Connectivity

  
Public Peering This location offers Equinix PAIX Services
Equinix Carrier Room

AT&T
Level3
Time Warner Telecom
Cogent

Abovenet
FiberLight
AGL