- Switch and Data control room houses manager's office and security personnel/equipment
- Open space for cabinets
- Private cages available
- Top-quality, electrostatic dissipative raised floor tiles designed for 175 psf, and in some facilities 300 lbs. psf, floor load
- Meet all code specifications for safety and electrical grounding, per NFPA 70
- DC power and communication cabling tray pathways
- Optical fiber guide conveyance system
- Heavy load freight elevators or loading dock access to the space
- Comprehensive and flexible cabling infrastructure
|
Security & Access |
X |


|
- 24/7 security management via the Security Operations Center (SOC)
- Remote camera monitoring 24/7, backed by digital recordings on file for 30 days
- Access to equipment area 24/7 days via card key and pass code only
- Escort services 24/7 at sites with non-secured equipment areas
- Locking cabinets and/or cages
- Full CCTV surveillance
- BMS equipment monitoring system supported by Switch and Data's 24x7 operations center
|
Power Infrastructure |
X |


|
- High-density power and cooling for the latest generation of servers
- Up to 200 watts per square foot including HVAC
- 120/208V AC and -48V DC available
- 100% generator backup
- Generator capacity designed to multiple 1 to 2 MgWATT Generators
- Size of fuel tank 1,000 to 10,000 gallons
- Generator both auto start and auto transfer. Isolation bypass feature on automatic transfer switch
- Minimum 24-hour run time fuel capacity Two-hour response for fuel delivery
- UPS backup power
- Voltage output 480 transformed to 120/208 V
- -48 Volt DC Battery Plant
- 1200 amp expandable to 10,000 amp
- 2-hour battery reserve non-redundant, 4 hours redundant
- "True" A/B power feeds
- Grounding in accordance with NFPA 70
|
Environmental Controls |
X |


|
- Under-floor cooling provided by computer-room grade equipment
- Cooling not less than 300 BTU/h per square foot with an N+1 redundancy
- Temperature is maintained at 72 degrees F dry bulb at ASHRAE 1%
- In the event of a power interruption HVAC systems (and entire facility) operate on diesel generators
- 30% to 60% humidity non-condensing. Humidity control delivered through ATS/Liebert units via infra-red humidifier
|
Interconnection Options |
X |


|
- Switch and Data managed Meet Me Room (MMR) in most sites to facilitate interconnection
- Broad choice of leading fiber and circuit carriers in each facility
- Pre-run conduit assures rapid connection to new carriers. Large number of access providers in buildings assures the lowest possible telecommunication link charges
- Access providers are encouraged to locate muxes within Switch and Data site to facilitate interconnectivity
- Overhead cable trays are provided for connectivity
- Layer 2 switching architecture for public interconnection and peering at select locations
- 24x7 diagnostic remote switch fabric and port monitoring
|
Fire Detection & Suppression |
X |

|
- Dry-pipe pre-action sprinkler rated for telecommunication equipment/computer room
- Integrated smoke/heat detector system
- Under-floor leak detection system
|