Building Specs
The Switch and Data Detroit data center is a one-story building just 300 feet from SBC and the relay station. This site features 12,000 square feet of colocation space and multiple connectivity options.
|
| | |
| Square Feet | 12,000 |
| Floor Load | 100 pounds per square foot |
| Ceiling Height | Nine feet three inches above raised floor |
| Roof Rights | Roof rights available |
| Line of Site | Clear line of sight in all directions |
| NPA-NXX | 248-353 |
| Fiber | Two diverse fiber entry points |
| Fiber Conduits | Twelve 4-inch conduits |
| Fiber Innerducts | Forty-eight innerducts, four 1-inch innerducts/conduit |
| Points of Entry | 24 – 1” per entry point |
| KVM Cart | KVM cart available upon request |
| | |
 |
| | |
Environmental Controls |
| | |
| Fire Supression | Pre-action, dry pipe sprinkler system |
| HVAC | A/C units maintain a climate of 72 degrees (+/- 5) and 30-60% humidity |
 |
| | |
Power Systems |
| | |
| Power Redundancy | 1200 amp AC switchgear, 225 KVA UPS module built to 450KVA capacity with N+1 redundancy; 2400 amp DC power system. |
| Standby Generator | Dedicated 750 kW standby generator |
| | |
 |
| | |
Security Systems |
| | |
| Security Systems | Real-time video surveillance with 24x7 monitoring, mantrap, card key access, alarm/key monitoring, and CCTV surveillance |
 |
| | |
Connectivity |
| | |
| Switch and Data MMR |
AT&T (SBC)
Bullseye
Cogent Communications
Level 3
McLeod USA
Sigecom
SingleCNXT
US Signal
Waveform Technology
XO Communications
|
| | |