Building Specs
Equinix operates International Business
Exchange™ (IBX®) data centers in
strategic metropolitan markets in North
America, Europe, and Asia-Pacific. These
IBX centers serve as a reliable and secure
destination for the world’s most powerful
networks and companies. It’s what we do
every day—without compromise.
Equinix operates state of the art IBX
centers in the Los Angeles metro
area in a campus environment and offers
a full range of premium colocation,
interconnection and support services
to a wide range of networks, enterprise,
content companies and financial
institutions.
Los Angeles is home to many of our Internet content and entertainment
customers, such as motion pictures,
television, Internet content, video games,
and recorded music firms. With network traffic growing exponentially because of the increasingly prevalent use of video on the Web, Equinix’s IBX centers in the Los Angeles area have been key to the network strategies of Internet content
and entertainment companies looking to
reach their end-users quickly. Equinix’s
unique mix of networks, ISPs, and content companies makes it an ideal place to reach business partners and eyeball networks cost-effectively and quickly.
|
| | |
| Square Feet | 62,159 |
| Satellite Platform |
N/A |
| Flex Space |
11,800 |
| Floor Load |
250 psf |
| NPA-NXX | 310-414 |
| | |
 |
| | |
Environmental Controls |
| | |
| Fire Supression | Pre-action, dry pipe sprinkler system |
| HVAC |
A/C units maintain a climate of 70 degrees (+/- 5) and 30-60% humidity, N+1 redundancy |
| | |
 |
| | |
Power Systems |
| | |
| Electrical Capacity |
4.0 kVA per cabinet |
| UPS Configuration |
6.72 MW UPS supportable loads (N+1) |
| # of Utility Feeders |
1 - provisioned for 2 |
| # of Power Transformers |
6 (each transformer is rated at 3,000 kVA) |
| Utility Voltage |
16 KV (Site will utilize 66 KV primary voltage after completion of
new 56 MVA, 66 KV/16 KV Substation—tentatively Q3 2010) |
| Standby Power |
7 - 2,500 kW dieselengine generator power (12,500 kW
operating, 5,000 kW standby) |
| Standby Power Config. |
(N+1) - 5 primary, 1 reserve and 1 swing redundant generator. Each generator unit is 2,500 kW/3,125 kVA. |
| | |
 |
| | |
Security Systems |
| | |
| Physical |
“Man trap” entry |
| Human |
24x7 security gaurds |
| Electronic |
CCTV and Recorders, Motion Detection, Hand Geometry
Readers, Fiber Vault |
| |
|
 |
| | |
Connectivity |
| | |
| Cross Connects |
Single-Mode Fiber
Multi-Mode fiber (62.5 and 50 micron)
CAT5
CAT6
CAT5 (T1)
CAT3 (POTS)
|
| IBXLink |
Extends choice and reach for carrier and network availability across metro areas |
| Equinix Exchange™ |
Automated network provisioning, multi-homing and billing |
| Equinix Carrier Ethernet Exchange |
Enables Ethernet Service Providers to interconnect to CENs and expand the reach of Ethernet services |
| Equinix Direct™ Available |
Automated network provisioning, multi-homing and billing |
| | |