North Bergen, New Jersey Data Center
5851 West Side Avenue, North Bergen, NJ 07047, USA
 |
Building Specs
The North Bergen site was originally built in 1985 and utilized as a disaster recovery facility. Since its acquisition, Switch and Data has built this site to their high-performance data center standard and can supply more than 200 watts per square foot of power and cooling capacity. At full completion this site will add more than 163,000 gross square feet to Switch and Data’s New York Metro data center capacity, bringing the company’s data center capacity in the market to more than 250,000 gross square feet. Switch and Data has interconnected this new site to its existing 111 8th Avenue and 60 Hudson Street sites in New York, providing access to more than 300 networks and making it one of the most densely interconnected data centers in North America. It is also a multi level three story stand alone building with access to the New Jersey Turnpike, GWB and Lincoln Tunnel.
|
| | |
| Square Feet | 163,537 |
| Floor Load | Live Load Ex. 175#/sf first and second floors, 100 #/sf third floor |
| Roof Rights | Roof rights available |
| Product Availability |
- Cage Space Available
- Cabinets Available
- UPS Power Available
- DC Power Available
- Standard Cross Connects --- DS0, DS1, DS3, Ethernet, Fiber
- Metro Cross Connects --- (access to meet-me-rooms in NYC 111 8th and 60 Hudson) --- Ethernet, GigE
- PAIX Ports --- 100 Mbps, 333 Mbps (Fractional GigE), 500 Mbps (Half GigE), 1000 Mbps or Gigabit
- Ethernet (GigE), NxGigE 2-4-6-8, 10 GigE 6-8, 10 GigE
- SingleCNXT-i (Internet Acess) --- Access to bandwidth providers in NYC 111 8th and 60 Hudson
- TechSmart® (Remote Hands): 24/7/365 Technical Support
- Network Timing: GPS (primary) and CDMA (redundant) time source
|
| | |
 |
| | |
Environmental Controls |
| | |
| Fire Supression |
- Pre-Action double interlock fire suppression system
- Dual zoned smoke and heat fire alarm detection system
|
| HVAC |
- 14259 KW of Heat Rejection Capacity
- Interior and exterior systems are each deployed at N + 1
- A/C units maintain a climate of 72 degrees (+/- 5) and 30-60% humidity (SLA Statement)
|
| Alarm Monitoring |
- All essential equipment is tied into Falcon Alarm System (UPS, DC plant, PMMs, BDCBBs, ATS’s, Generators, Diesel tanks, TVSS, Fire System)
- Operations Alarm Management (OAM) Group monitors facility falcon units 24/7/365
- Alarming is a dry contact system set to normally closed
|
 |
| | |
Power Systems |
| | |
| Power Density | 200 Watts Per Sq. Ft. |
| UPS System |
- Eight parallel UPS systems configured N+1
- Primary UPS systems provide 13568 kW
- UPS System deployed to carry full design load 12 --- 15 minutes
- 17,638 kW of UPS sub-distribution infrastructure
|
| DC Plant |
- Six redundant DC plant systems
- Each DC System is deployed as A & B plants design classification as 2N
- Primary DC power systems provide 691 kW
- 1037 kW of matching DC sub-distribution infrastructure
- DC Plant systems are deployed to carry full load for 4 hours via dedicated battery banks per DC plant
- -48 Volt DC Battery Plant
- 2400 amp expandable to 10,000 amp
- 2-hour battery reserve non-redundant, 4 hours redundant
- ‘‘True’’ A/B Power feeds
|
| Standby Generator |
- 2000 kW generators configured in N
- 24 hours of continuous generator run time at full design load
- Generator systems both auto start and auto transfer
|
| | |
 |
| | |
Security Systems |
| | |
| Security Systems |
- Card access control at all secure areas/doors
- Surveillance cameras at strategic locations, exterior and interior CCTV coverage
- Fully fenced and secure perimeter
- 24/7 On-site security personnel
- 24/7 Corporate security surveillance
- Speaker and Phone Systems installed throughout facility for correspondence with local and remote
- security personnel
- 30 days of on-site video back-up
|
 |
| | |
Connectivity |
| | |
| Public Peering |
- Big Fish Networks
- This location offers Switch and Data PAIX Services
|
| | |
| Switch and Data MMR |
- Abovenet
- Cablevision Lightpath
- Cogent Communications
- Hibernia Atlantic
- InterNap
- IPC Network Services
- Level3
- Reliance Globalcom
- Verizon Business (MCI)
- Access to the carriers in the meet-me-rooms in NYC 111 8th and 60 Hudson
|
| | |
|
|
|