North Bergen, New Jersey Switch and Data Data Center
 

Skip Navigation Links

 
Atlanta Boston Buffalo Chicago Cleveland Dallas 2323 Bryan Dallas 4101 Bryan Dallas INFOMART Denver Detroit Indianapolis Los Angeles Miami 1st Miami 2nd Nashville New Jersey NYC 60 Hudson NYC 65 Broadway NYC 111 8th Palo Alto Philadelphia Broad Philadelphia Market Phoenix Pittsburgh Reston Saint Louis San Jose Seattle 3rd Seattle 6th Sunnyvale Tampa Toronto Vienna SAIC Vienna Tyco

North Bergen, New Jersey Data Center

5851 West Side Avenue, North Bergen, NJ 07047, USA

Download Fact Sheet

North Bergen, New Jersey Data Center

North Bergen Site Tour Video:




See other New York Metro sites:

Data Center Building Specs

Building Specs

The North Bergen site was originally built in 1985 and utilized as a disaster recovery facility. Since its acquisition, Switch and Data has built this site to their high-performance data center standard and can supply more than 200 watts per square foot of power and cooling capacity. At full completion this site will add more than 163,000 gross square feet to Switch and Data’s New York Metro data center capacity, bringing the company’s data center capacity in the market to more than 250,000 gross square feet. Switch and Data has interconnected this new site to its existing 111 8th Avenue and 60 Hudson Street sites in New York, providing access to more than 300 networks and making it one of the most densely interconnected data centers in North America. It is also a multi level three story stand alone building with access to the New Jersey Turnpike, GWB and Lincoln Tunnel.

  
Square Feet163,537
Floor LoadLive Load Ex. 175#/sf first and second floors, 100 #/sf third floor
Roof RightsRoof rights available
Product Availability
  • Cage Space Available
  • Cabinets Available
  • UPS Power Available
  • DC Power Available
  • Standard Cross Connects --- DS0, DS1, DS3, Ethernet, Fiber
  • Metro Cross Connects --- (access to meet-me-rooms in NYC 111 8th and 60 Hudson) --- Ethernet, GigE
  • PAIX Ports --- 100 Mbps, 333 Mbps (Fractional GigE), 500 Mbps (Half GigE), 1000 Mbps or Gigabit
  • Ethernet (GigE), NxGigE 2-4-6-8, 10 GigE 6-8, 10 GigE
  • SingleCNXT-i (Internet Acess) --- Access to bandwidth providers in NYC 111 8th and 60 Hudson
  • TechSmart® (Remote Hands): 24/7/365 Technical Support
  • Network Timing: GPS (primary) and CDMA (redundant) time source
  
Data Center Environmental Controlsl
  

Environmental Controls

  
Fire Supression
  • Pre-Action double interlock fire suppression system
  • Dual zoned smoke and heat fire alarm detection system
HVAC
  • 14259 KW of Heat Rejection Capacity
  • Interior and exterior systems are each deployed at N + 1
  • A/C units maintain a climate of 72 degrees (+/- 5) and 30-60% humidity (SLA Statement)
Alarm Monitoring
  • All essential equipment is tied into Falcon Alarm System (UPS, DC plant, PMMs, BDCBBs, ATS’s, Generators, Diesel tanks, TVSS, Fire System)
  • Operations Alarm Management (OAM) Group monitors facility falcon units 24/7/365
  • Alarming is a dry contact system set to normally closed
Data Center Power Systems
  

Power Systems

  
Power Density200 Watts Per Sq. Ft.
UPS System
  • Eight parallel UPS systems configured N+1
  • Primary UPS systems provide 13568 kW
  • UPS System deployed to carry full design load 12 --- 15 minutes
  • 17,638 kW of UPS sub-distribution infrastructure
DC Plant
  • Six redundant DC plant systems
  • Each DC System is deployed as A & B plants design classification as 2N
  • Primary DC power systems provide 691 kW
  • 1037 kW of matching DC sub-distribution infrastructure
  • DC Plant systems are deployed to carry full load for 4 hours via dedicated battery banks per DC plant
  • -48 Volt DC Battery Plant
  • 2400 amp expandable to 10,000 amp
  • 2-hour battery reserve non-redundant, 4 hours redundant
  • ‘‘True’’ A/B Power feeds
Standby Generator
  • 2000 kW generators configured in N
  • 24 hours of continuous generator run time at full design load
  • Generator systems both auto start and auto transfer
  
Data Center Power Systems
  

Security Systems

  
Security Systems
  • Card access control at all secure areas/doors
  • Surveillance cameras at strategic locations, exterior and interior CCTV coverage
  • Fully fenced and secure perimeter
  • 24/7 On-site security personnel
  • 24/7 Corporate security surveillance
  • Speaker and Phone Systems installed throughout facility for correspondence with local and remote
  • security personnel
  • 30 days of on-site video back-up
Data Center Connectivity
  

Connectivity

  
Public Peering
  • Big Fish Networks
  • This location offers Switch and Data PAIX Services
  
Switch and Data MMR
  • Abovenet
  • Cablevision Lightpath
  • Cogent Communications
  • Hibernia Atlantic
  • InterNap
  • IPC Network Services
  • Level3
  • Reliance Globalcom
  • Verizon Business (MCI)
  • Access to the carriers in the meet-me-rooms in NYC 111 8th and 60 Hudson