Building Specs
Facility originally built in 1999 and utilized as a Carrier Datacenter. Facility upgraded in 2008 to Equinix high-performance data center standard and can supply more than 200 watts per square foot of power and cooling capacity. It is a two story stand alone building with access to Highways 85, 101, 237, and 880 and the Light Rail System.
|
| | |
| Square Feet | 41,867 |
| Floor Load | 80 lbs / sq ft |
| Roof Rights | Roof rights available |
| CLLI | SNVBCACY |
| NPA-NXX | 408-400 |
| Product Availability |
- Cage Space Available
- Cabinets Available
- UPS Power Available
- DC Power Available
- Standard Cross Connects --- DS0, DS1, DS3, Ethernet, Fiber
- Metro Cross Connects --- DS1, DS3, Ethernet, GigE (Palo Alto, San Jose)
- PAIX Ports --- Metro PAIX to all Bay Area PAIX sites: Palo Alto, San Jose, San Francisco 200 Paul, and San Jose Market Post Tower - Sunnyvale and Palo Alto connected by a diverse fiber ring
- SingleCNXT-i (Internet Access)
- TechSmart® (Remote Hands): 24/7/365 Technical Support
- Roof Space
- Network Timing: GPS (primary) and CDMA (redundant) time source
|
| Certification | SAS 70 Type II Compliant |
| | |
 |
| | |
Environmental Controls |
| | |
| Fire Supression | Pre-Action double interlock fire suppression system |
| HVAC |
- 1722 KW of Heat Rejection Capacity
- (21) Primary and (6) Redundant CRAC Units
- 512 Tons of Primary Cooling
- A/C units maintain a climate of 72 degrees (+/- 5) and 30-60% humidity
|
| Alarm Monitoring |
- All essential equipment is tied into Falcon Alarm System (UPS, DC plant, PMMs, BDCBBs, ATS’s, Generators, Diesel tanks, TVSS, Fire System)
- Operations Alarm Management (OAM) Group monitors facility falcon units 24/7/365
- Alarming is a dry contact system set to normally closed
|
| Seismic |
- Seismic Zone 4 with importance factor in excess of 1.25
- Concrete tilt-up with steel column construction
- Steel seismic bracing
- All cabinet and racks are installed with seismic bracing
- All mechanical, electrical, HVAC systems are seismically braced including ductwork, piping, conduits and CRAC units
|
 |
| | |
Power Systems |
| | |
| Power Density |
- 200 Watts Per Sq. Ft.
- (5) 500 KVA UPS units in parallel N+1 configuration
|
| UPS System |
- Each UPS unit can support its designed full load for 15 minutes via internal battery plant
- (10) AC Distribution Units
- 1200 Amp Parallel 2N system
|
| DC Plant |
- (2) DC Distribution Units
- Each DC Plant can support its designed full load for 4 hours via internal battery plants
- (3) 1.25MW and (1) 2MW Generators in N+1 Design
|
| Standby Generator |
- 10,000 gallons of diesel storage on site to provide a minimum of 24 hours of continuous generator run time
- (2) Diesel vendor contracts in place with 4 hour SLAs
- Generator Farm is located in environmentally protected secured enclosure
|
| | |
 |
| | |
Security Systems |
| | |
| Security Systems |
- Card access control at all secure areas/doors
- Surveillance cameras at strategic locations, exterior and interior CCTV coverage
- Fully fenced and secure perimeter
- 24/7 On-site security personnel
- 24/7 Corporate security surveillance
- Speaker and Phone Systems installed throughout facility for correspondence with local and remote security personnel
- 30 days of on-site video back-up
|
 |
| | |
Connectivity |
| | |
| Public Peering |
Abovenet
Cogent |
Global Crossing
XO Communications
|
| | |