Building Specs
Building is over 25 years old and serves as a datacenter for multiple companies.
|
| | |
| Square Feet | 44,382 |
| Floor Load | Rating = Live Load Ex. 200#/sf |
| Roof Rights | Roof rights available |
| Product Availability |
- Cage Space Available
- Cabinets Available
- UPS Power Available
- DC Power Available
- Standard Cross Connects --- DS0, DS1, DS3, Ethernet, Fiber
- PAIX Ports – 100 Mbps, 333 Mbps (Fractional GigE), 500 Mbps (Half GigE), 1000 Mbps or Gigabit Ethernet (GigE), NxGigE 2-4-6-8, 10 GigE 6-8, 10 GigE
- SingleCNXT-i (Internet Access)
- TechSmart® (Remote Hands): 24/7/365 Technical Support
- Roof Space
- Network Timing: GPS (primary) and CDMA (redundant) time source
|
| Certification | SAS 70 Type I Compliant |
| | |
 |
| | |
Environmental Controls |
| | |
| Fire Supression |
- Pre-Action double interlock fire suppression system
- Multi zoned smoke and heat fire alarm detection system
|
| HVAC |
- 1100 Tons of Heat Rejection Capacity
- Interior and exterior systems are each deployed at N + 1
- A/C units maintain a climate of 72 degrees (+/- 5) and 30-60% humidity (SLA Statement)
|
| Alarm Monitoring |
- All essential equipment is tied into Falcon Alarm System (UPS, DC plant, PMMs, BDCBBs, ATS’s, Generators, Diesel tanks, TVSS, Fire System)
- Operations Alarm Management (OAM) Group monitors facility falcon units 24/7/365
- Alarming is a dry contact system set to normally closed
|
| Seismic |
- Seismic Zone -- with importance factor in excess of 1.25
- Concrete tilt-up with steel column construction
- Steel seismic bracing
- All cabinet and racks are installed with seismic bracing
- All mechanical, electrical, HVAC systems are seismically braced including ductwork, piping, conduits and CRAC units
|
 |
| | |
Power Systems |
| | |
| Power Density | 200 Watts Per Sq. Ft. of equipment floor |
| UPS System |
- Four parallel UPS systems configured N+1
- Primary UPS systems provide 1300Kva
- UPS System deployed to carry full design load 12 – 15 minutes
|
| DC Plant |
- Fully redundant DC plant system
- System is deployed as A & B plants design classification as N+1
- 6400 amps of matching DC sub-distribution infrastructure
- DC Plant systems are deployed to carry full load for 4 hours via dedicated battery banks per DC plant
- -48 Volt DC Battery Plant
- 6400 amp expandable to 10,000 amp
- 2-hour battery reserve non-redundant, 4 hours redundant
|
| Standby Generator |
- Three 1250 KVA Generators (critical load) Five 750 KVA generators (mechanical load)
- Two 20,000 gallon underground fuel tanks
- Generator systems both auto start and auto transfer(building owned)
|
| | |
 |
| | |
Security Systems |
| | |
| Security Systems |
- Card access control at all secure areas/doors
- Surveillance cameras at strategic locations, exterior and interior CCTV coverage
- Fully fenced and secure perimeter
- 24/7 On-site security personnel
- 24/7 Corporate security surveillance
- Speaker and Phone Systems installed throughout facility for correspondence with local and remote security personnel
- 30 days of on-site video back-up
|
 |
| | |
Connectivity |
| | |
| Public Peering | This location offers Switch and Data PAIX Services |
| | |
| Switch and Data MMR |
AboveNet
Allied Telecom
Cogent
Cox Communications
Fiberlight
Fibergate
Internap
Ironpath
Level3 (Wiltel, Progress Telecom, Looking Glass)
MegaPath
|
Neon (RCN)
Qwest (On Fiber & Telcove)
PPL (Cambrian)
Reliance Globalcom
SingleCNXT
Verizon (MCI)
Video Presence
XO Communications
Yipes
Zayo Bandwidth
|
| | |